GSH13
1½- To 5-Ton SpliT SySTem HeaT pumpS
13 SeeR / R-22
Contents
Nomenclature....................................... 2
Product Specifications .......................... 3
AHRI Ratings.......................................... 4
Dimensions ........................................... 5
Wiring Diagrams ................................... 6
Accessories ............................................ 7
Standard Features
Cabinet Features
•
•
•
•
Energy-efficient compressor
Quiet condenser fan system
Copper tube/aluminum fin coil
For use with R-22 refrigerant and
charged with inert gas for shipping
Factory-installed bi-flow liquid line filter drier
Low-pressure switch
Time-initiated, temperature-
terminated defrost control
Service valves with sweat connec-
tions and easy-access gauge ports
Contactor with lug connection
Ground lug connection
•
•
•
Louver design sound control top
Steel louver coil guard
Heavy-gauge, galvanized-steel
cabinet with rust-resistant screws
•
•
•
Attractive Architectural Gray powder-paint
finish with 500-hour salt-spray approval
Single-panel access to controls with space
provided for field-installed accessories
When properly anchored, meets the
2010 Florida Building Code unit integrity
requirements for hurricane-type winds
(Anchor bracket kits available.)
•
•
•
•
•
•
•
ETL Listed
* Complete warranty details available
from your local dealer or at www.
goodmanmfg.com.
SS-GSH13
11/13
Supersedes 9/13
Product SPecificationS
SpecificaTionS
GSH13
0181C*
GSH13
0241C*
GSH13
0301C*
GSH13
0361C*
GSH13
0421B*
GSH13
0481B*
GSH13
0601A*
Capacities and Ratings
Tonnage
1½
73
2
2½
72
3
3½
76
4
5
Decibels
71
71
76
77
Compressor
RLA
8.3
40.3
Scroll
10.8
56.0
13.5
68.0
14.1
75.0
19.2
112.0
Scroll
19.9
104.0
Scroll
25.0
148.0
Scroll
LRA
Type
Scroll
Scroll
Scroll
Condenser Fan Motor
Horsepower
1/8
0.7
1/8
0.7
1/8
0.7
¼
¼
¼
1/6
1.1
FLA
1.5
1.5
1.5
Refrigerant System
Refrigerant Line Size
Liquid Line Size (“O.D.)
Sucꢀon Line Size (“O.D.)
Refrigerant Connecꢀon Size
Liquid Valve Size (“O.D.)
Sucꢀon Valve Size (“O.D.)
Valve Type
⅜"
¾"
⅜"
¾"
⅜"
¾"
⅜"
⅞"
⅜"
⅜"
⅜"
1⅛"
1⅛"
1⅛"
⅜"
¾"
⅜"
¾"
⅜"
¾"
⅜"
⅞"
⅜"
⅞"
⅜"
⅞"
⅜"
⅞"
Sweat
127
Sweat
122
Sweat
130
Sweat
188
Sweat
246
Sweat
208
Sweat
233
Refrigerant Charge
Electrical Data
Voltage-Phase (60 Hz)
Minimum Circuit Ampacity ²
Max. Overcurrent Protecꢀon ³
Min / Max Volts
208/230-1
11.1
208/230-1
14.2
208/230-1
17.6
208/230-1
19.1
208/230-1
25.5
208/230-1
26.4
208/230-1
32.3
15
25
30
30
40
45
50
197/253
½" or ¾"
142
197/253
½" or ¾"
147
197/253
½" or ¾"
146
197/253
½" or ¾"
146
197/253
½" or ¾"
152
197/253
½" or ¾"
152
197/253
½" or ¾"
278
Electrical Conduit Size
Equipment Weight (lbs)
Ship Weight (lbs)
159
164
164
164
170
170
300
¹
Tested and rated in accordance with AHRI Standard 210/240
²
³
Wire size should be determined in accordance with Naꢀonal Electrical Codes; extensive wire runs will require larger wire sizes
Must use ꢀme-delay fuses or HACR-type circuit breakers of the same size as noted.
Notes
•
•
•
•
Always check the S&R plate for electrical data on the unit being installed.
Installer will need to supply ⅞” to 1⅛” adapters for sucꢀon line connecꢀons.
Charge to be added for 15’ of ⅜” liquid line. System charge must be adjusted per Installaꢀon Instrucꢀons Final Charge Procedure.
Installaꢀon of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECI-
FIED TXV IS DETERMINED BY THE OUTDOOR UNIT NOT THE INDOOR COIL.
SS-GSH13
3
Product SPecificationS
aHRi RaTinGS
Cooling Capacity¹
TVA Ratings⁴
Total Sens.
Heating Capacity¹
High HSPF⁵ Low
Outdoor
Unit
Indoor
Unit
SEER² EER³
CFM
AHRI #
Total
Sens.
GSH130484A*
GSH130601A*
GSH130603A*
GSH130604A*
AR*F486016B*
AR*F486016B*
AR*F486016B*
AR*F486016B*
45,000 33,800 13.0 11.0 41,500 31,800 43,000 8.2 27,000 1,600 1492572
55,500 41,000 13.0 11.0 51,500 37,000 55,500 8.5 35,000 1,800 1492576
55,500 41,000 13.0 11.0 51,500 37,000 55,500 8.5 35,000 1,800 1492581
55,500 41,000 13.0 11.0 51,500 37,000 55,500 8.5 35,000 1,800 1492585
GSH130241(B,C)* AR*F182416B*+TXV 23,000 17,800 13.0 11.0 21,400 15,800 21,400 7.7 11,800 860 4675037
GSH130301(B,C)* AR*F363616B*
GSH130181(B,C)* AR*F182416B*
GSH130361(B,C)* AR*F374316B*
27,800 20,200 13.0 11.0 25,800 19,300 25,400 7.7 15,300 1,020 4692016
17,600 13,100 13.0 11.0 16,300 11,800 16,800 7.7 8,900 625 4675036
33,600 26,200 13.0 11.0 31,000 23,400 31,400 7.7 18,200 1,260 4692017
55,500 41,500 13.0 11.0 51,500 37,000 55,500 8.5 35,000 1,800 4982919
45,000 33,800 13.0 11.0 41,500 31,800 43,000 8.2 27,000 1,600 5528480
40,000 29,800 13.0 11.0 37,200 28,200 39,000 8.0 23,000 1,250 5528479
33,600 26,200 13.0 11.0 31,000 23,400 31,400 7.7 18,200 1,260 5528484
45,000 33,800 13.0 11.0 41,500 31,800 43,000 8.2 27,000 1,600 5528481
45,000 33,200 13.0 11.0 41,500 31,800 43,000 8.2 27,000 1,600 5528482
GSH130604AC
GSH130481B*
GSH130421B*
GSH130363A*
GSH130483B*
GSH130484AD
AR*F486016B*
AR*F486016B*
AR*F364216B*
AR*F374316B*
AR*F486016B*
AR*F486016B*
¹
³
BTU/h
Energy Efficiency Raꢀo @ 80°F/ 67°F/ 95°F
²
Seasonal Energy Efficiency Raꢀo; Cerꢀfied per AHRI 210/240 @ 80°F/ 67°F/ 95°F
TVA Raꢀng: BTU/h @ 75°F/ 63°F - 95°F HSPF = Heaꢀng Seasonal Performance Factor
⁴
⁵
Notes
•
•
•
Always check the S&R plate for electrical data on the unit being installed.
When matching outdoor unit to indoor unit, use the piston supplied with outdoor unit or that specified on the piston kit chart supplied with the indoor unit.
EEP - Order from Service Dept. Part No. B13707-38 or new Solid State Board B13707-35S. Part No. B13707-38 is not in-
terchangeable with B13707-35S. The Goodman Gas Furnace contains the EEP cooling ꢀme delay
4
SS-GSH13
Product SPecificationS
DimenSionS
W
D
H
Dimensions
Model
W”
26
D”
26
H”
GSH130181C
GSH130241C
GSH130301C
GSH130361C
GSH130421B
GSH130481B
GSH130601A
32¼
32¼
34¾
38¼
32¼
34¾
34¾
26
26
29
29
29
29
29
29
29
29
35½
35½
SS-GSH13
5
Product SPecificationS
WiRinG DiaGRam
Y
N L O R O T C A T N C O E L O P
E L B U O D E A T N E T R A L
6
SS-GSH13
Product SPecificationS
acceSSoRieS
GSH13
018
GSH13
024
GSH13
030
GSH13
036
GSH13
042
GSH13
048
GSH13
060
Model
Description
Anchor Bracket Kit *
ABK-20
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
ASC01
Anꢀ-Short Cycle Kit
Hard-start Kit
CSR-U-1
CSR-U-2
CSR-U-3
FSK01A¹
OT/EHR18-60
Hard-start Kit
Hard-start Kit
X
X
X
X
Freeze Protecꢀon Kit
Emergency Heat Relay kit
Outdoor Thermostat with Lockout Stat
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
OT18-60A²
*
Contains 20 brackets; four brackets needed to anchor unit to pad
¹
Installed on indoor coil
²
³
Required for heat pump applicaꢀons where ambient temperatures fall below 0 °F with 50% or higher relaꢀve humidity.
Condensing units and heat pumps with reciprocaꢀng compressors require the use of start-assist components when used in conjuncꢀon with an indoor
coil using a non-bleed thermal expansion valve refrigerant metering device. The TXV should always be sized based on the tonnage of the outdoor unit.
SS-GSH13
7
Product SPecificationS
noTeS
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without
notice or without incurring obligations. © 2013 • Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA.
8